Viessmann Boiler: Check the fixed high limit via the TUV button
Check the fixed high limit via the TUV button on a Viessmann boiler: The adjustable high limit R is bridged for this check. A minimum supply is needed during the test. Recirculated water should be at least 10% of the rated load amount, and heat use should be reduced as far as possible. The burner runs until the fixed high limit cuts it off at the safety temperature.
Applies to: Vitotronic 100 GC1 fixed high limit check
How to fix check the fixed high limit via the tuv button: step by step
- Hold the TUV button continuously pressed during the check.
- Run the burner until boiler water reaches the safety temperature and the fixed high limit operates.
- Release the TUV button once the burner has switched off.
- Wait until boiler water has dropped 15 to 20 °C (27 to 36 °F) below the selected safety temperature.
- Reset the fixed high limit by pressing the E button.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 installation and service instructions, p. 86. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.