Viessmann Boiler: Check the fixed high limit (TÜV TEST)

Updated · by Aurora Star Tech Inc.

Check the fixed high limit (TÜV TEST) on a Viessmann boiler: Test the boiler's fixed high limit cut-out by bridging the adjustable high limit while the boiler heats up.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 300 GW2 on Viessmann boilers

How to fix check the fixed high limit (tÜv test): step by step

  1. Make sure a minimum supply is running. Recirculated water should be at least 10% of the flow at rated load.
  2. Reduce the heat consumption as far as possible.
  3. Press and hold the TÜV TEST button for the whole check. The adjustable high limit is bridged.
  4. Let the burner run until the boiler water reaches the safety temperature and the fixed high limit trips.
  5. Release the TÜV TEST button and let the boiler water drop 15 to 20°C (27 to 36°F) below the selected safety temperature.
  6. Reset the fixed high limit with the E button.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitotronic 300 GW2 installation and service instructions, p. 64-65. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.