Viessmann Boiler: Check the condensate drain and clean the siphon
Check the condensate drain and clean the siphon on a Viessmann boiler: If condensate cannot drain freely it builds up in the bottom of the boiler and the burner shuts down with a fault message.
Applies to: Condensate drain and siphon
Common causes of check the condensate drain and clean the siphon
- Condensate not draining freely from the siphon
- Debris in the siphon trap
- Condensate pipe incorrectly connected to the siphon or heat exchanger
How to fix check the condensate drain and clean the siphon: step by step
- Check that condensate drains freely in the siphon.
- Pull off retaining clip A.
- Pull filler pipe B upwards.
- Pull trap C downwards.
- Disconnect the condensate hose from trap C.
- Clean the siphon.
- Fill the siphon with water and reassemble.
- Check that the condensate pipe is connected correctly to the siphon and heat exchanger.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 222-F B2TB 19, 35, 68, 125 Service Instructions, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.