Viessmann Boiler: Check supply temperature sensor or low-loss header sensor

Updated · by Aurora Star Tech Inc.

Check supply temperature sensor or low-loss header sensor on a Viessmann boiler: Only one of these sensors may be used.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA

Common causes of check supply temperature sensor or low-loss header sensor

  • Sensor resistance deviates severely from the curve

How to fix check supply temperature sensor or low-loss header sensor: step by step

  1. Pull plug X3 from the control unit.
  2. Check resistance across terminals X3.4 and X3.5.
  3. Compare with the curve (NTC 10 kΩ).
  4. Replace the sensor if the deviation is severe.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 200-W B2HA service instructions, p. 85. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.