Viessmann Boiler: Check supply/return water temperature sensor

Updated · by Aurora Star Tech Inc.

Check supply/return water temperature sensor on a Viessmann boiler: Measure the strap-on sensor resistance and compare it with the water temperature.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Supply and return water temperature sensor

How to fix check supply/return water temperature sensor: step by step

  1. Disconnect the sensor plug in the terminal compartment.
  2. Measure the resistance at terminals 1 and 2 of the plug.
  3. Compare the reading with the current water temperature using the table.
  4. If the values differ significantly, check the installation.
  5. Replace the sensor if the installation is correct and the reading is still wrong.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B

Source: Vitotronic 200 service instructions, p. 72. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.