Viessmann Boiler: Check supply or return temperature sensor
Check supply or return temperature sensor on a Viessmann boiler: Strap-on or immersion sensor for supply or return temperature. Connection is shown on pages 58 and 59.
Applies to: Supply or return temperature sensor
How to fix check supply or return temperature sensor: step by step
- Remove the sensor plug (? , aJA or aJB).
- Check the resistance at terminals 1 and 2 of the plug.
- Compare with the displayed actual temperature (scanning is on page 91).
- Check the installation and replace the sensor if the deviation is severe.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 100 GC1 and 300-K MW1S installation and service instructions, p. 126. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.