Viessmann Boiler: Check strap-on or immersion supply/return sensor
Check strap-on or immersion supply/return sensor on a Viessmann boiler: Check resistance of the supply or return temperature sensor and compare with the displayed temperature.
Applies to: Strap-on and immersion temperature sensors
Common causes of check strap-on or immersion supply/return sensor
- Displayed temperature differs significantly from actual temperature
How to fix check strap-on or immersion supply/return sensor: step by step
- Remove plug 2/17.
- Measure resistance at terminals 1 and 2, or 2 and 3 if a return sensor is fitted.
- Compare the reading with the resistance table.
- Compare the value with the displayed actual temperature (see scanning on page 23).
- If the value differs significantly, check installation and replace the sensor if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H HK1M installation and service instructions, p. 35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.