Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Check safety valves, pumps and expansion vessel

Updated · by Aurora Star Tech Inc.

Check safety valves, pumps and expansion vessel on a Viessmann boiler: Confirm low water cut-offs, pressure relief valve and pumps work correctly. Check the pressure gauge, air vent and pressure relief valve. Refer to the maintenance instructions supplied by the component makers.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Safety valves, pumps, expansion vessel

Common causes of check safety valves, pumps and expansion vessel

  • Pressure relief valve leaking
  • Float type low water cut-off fouled
  • Diaphragm expansion vessel charge too low
  • Loss of water from leakage

How to fix check safety valves, pumps and expansion vessel: step by step

  1. Make sure the pressure relief valve does not leak and operates to the manufacturer's data.
  2. Check the pressure gauge and air vent.
  3. Flush float type low water cut-offs if used.
  4. Follow local rules for backflow preventers.
  5. If oil-lubricated system pumps are used, make sure they are lubricated.
  6. If motorized zone valves are used, follow their maintenance instructions.
  7. With the system cold, check the expansion vessel nitrogen pressure and system fill pressure (see the setting table for values).
  8. Repair all leaks. A lower manometer reading usually means water loss.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 222-F B2TB 19, 35, 68, 125 Service Instructions, p. 27. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977