Viessmann Boiler: Check return temperature sensor
Check return temperature sensor on a Viessmann boiler: Strap-on or immersion sensor for boiler return temperature. Plugs into socket 17A or 17B.
Applies to: Boiler return temperature sensor
How to fix check return temperature sensor: step by step
- Disconnect the sensor plug (aJA or aJB) in the boiler control terminal compartment.
- Measure the resistance between terminals 1 and 2 of the plug.
- Compare the reading with the current return temperature using the resistance table.
- If the value differs significantly, check the installation and replace the sensor if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 and 300-K MW1S installation and service instructions, p. 123. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.