Viessmann Boiler: Check outdoor temperature sensor
Check outdoor temperature sensor on a Viessmann boiler: Test the outdoor sensor resistance and compare it with the actual outdoor temperature.
Applies to: Outdoor temperature sensor
Common causes of check outdoor temperature sensor
- Sensor reads far from actual outdoor temperature
- Faulty wiring or plug connection
How to fix check outdoor temperature sensor: step by step
- Remove plug and check sensor resistance at terminals 1 and 2.
- Compare with the resistance table for the measured temperature.
- Disconnect wires from the sensor if values deviate severely from the curve, then repeat the measurement.
- Compare with the actual outdoor temperature shown on the display.
- Replace the cable or the outdoor sensor depending on the result.
- Scan the actual temperature again.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H HK1M installation and service instructions, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.