Viessmann Boiler: Check or change rotational direction of mixing valve motor
Check or change rotational direction of mixing valve motor on a Viessmann boiler: After power-up the boiler runs a self-test that opens and closes the mixing valve. If the flow temperature drops when the valve is opened, the motor direction or valve fitting is wrong.
Applies to: Mixing valve extension kit
Common causes of check or change rotational direction of mixing valve motor
- Motor turning in wrong direction
- Mixing valve set incorrectly fitted
How to fix check or change rotational direction of mixing valve motor: step by step
- Set the mixing valve manually to Open after the self-test.
- Confirm the flow temperature sensor reads a higher temperature.
- If the temperature drops, remove the upper casing cover of the extension kit.
- At plug gS, switch the cores at terminals '|' and '~'.
- Refit the casing cover.
- Disconnect main power before opening the boiler.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 88. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.