Viessmann Boiler: Check neutralization unit condensate pH

Updated · by Aurora Star Tech Inc.

Check neutralization unit condensate pH on a Viessmann boiler: Only applies where a neutralization unit is installed. The granulate is used up as it neutralizes the condensate.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB boiler with neutralization unit

Common causes of check neutralization unit condensate ph

  • Condensate pH below 6.5
  • Contaminated neutralization unit

How to fix check neutralization unit condensate ph: step by step

  1. Check condensate pH with a field-supplied pH measuring strip.
  2. If pH is below 6.5, replace the granulate.
  3. If the unit is contaminated, rinse it with tap water.
  4. Refill the granulate up to the red minimum fill marking.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199

Source: Vitodens 200-W B2HB service instructions, p. 27. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.