Viessmann Boiler: Check mixing valve motor rotation for extension kit
Check mixing valve motor rotation for extension kit on a Viessmann boiler: The boiler runs a self-test on power-up that opens and closes the mixing valve. If the flow temperature drops when the valve should open, the motor runs the wrong way or the valve set is fitted incorrectly.
Applies to: Vitodens 200-W B2HB
Common causes of check mixing valve motor rotation for extension kit
- Motor running in wrong direction
- Mixing valve set incorrectly fitted
How to fix check mixing valve motor rotation for extension kit: step by step
- Power up the boiler and let the self-test run.
- Set the mixing valve manually to Open.
- Check that the flow temperature sensor reads a higher temperature.
- If the temperature drops, reverse the motor rotation or check the valve set fitting.
- To reverse the rotation: remove the upper casing cover of the extension kit, swap the cores at terminals '|' and '~' at plug gS, and refit the casing cover.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Viessmann Vitodens 200-W B2HB service instructions, p. 85. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.