Viessmann Boiler: Check mixing valve motor rotation direction
Check mixing valve motor rotation direction on a Viessmann boiler: After power-up the boiler runs a self-test that opens and closes the mixing valve. Then the valve is set manually to Open to confirm the flow temperature rises.
Applies to: Vitodens 200-W B2HA extension kit
Common causes of check mixing valve motor rotation direction
- Motor turning in the wrong direction
- Mixing valve set incorrectly fitted
How to fix check mixing valve motor rotation direction: step by step
- Switch the boiler on and let the self-test run.
- Set the mixing valve manually to Open.
- Check that the flow temperature sensor reads a higher temperature.
- If the temperature drops, reverse the motor or refit the mixing valve set.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA service instructions, p. 86. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.