Viessmann Boiler: Check heating system, safety devices and water side
Check heating system, safety devices and water side on a Viessmann boiler: Routine checks of pressure, relief valve, expansion tank, low water cut-off and pumps.
Applies to: VR1 40 to 63, 161 to 245
How to fix check heating system, safety devices and water side: step by step
- Make sure all heating system and domestic hot water connections are pressure tight.
- Check the pressure gauge, air vent and pressure relief valve.
- Confirm the pressure relief valve does not leak and operates to the manufacturer's rating.
- Check the expansion tank, low water cut-off (if fitted) and pumps; follow the maintenance instructions supplied with each item.
- Flush float type low water cut-offs if used.
- With the system cold, confirm water fill pressure is between 10 and 15 psi. A lower reading usually means water loss.
- Repair all leaks. Follow the automatic fill valve instructions and local backflow preventer rules.
- Lubricate oil lubricated pumps.
- If an older non-diaphragm expansion tank is used, confirm the correct water level.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 installation and service manual, p. 50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.