Viessmann Boiler: Check heating control, mixing valve and low temperature protection
Check heating control, mixing valve and low temperature protection on a Viessmann boiler: Check that the control, mixing valve motor and low temperature protection package work correctly.
Applies to: Heating system control
Common causes of check heating control, mixing valve and low temperature protection
- Mixing valve may leak past the O-ring seals.
- Motorized arm may bind.
How to fix check heating control, mixing valve and low temperature protection: step by step
- Remove the motorized arm from the mixing valve and check the motor moves freely.
- If the mixing valve is not watertight, replace the O-rings.
- Snap the motorized arm back into place.
- Confirm the low temperature protection package operates correctly.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2A service instructions, p. 13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.