Viessmann Boiler: Check flue gas collector seals, lip seal and insulation
Check flue gas collector seals, lip seal and insulation on a Viessmann boiler: Look for leaks at the flue gas collector and the boiler flue connection. Condensate on the outside of the collector also indicates a leak.
Applies to: Vitocrossal 300 CU3A 26 to 199
Common causes of check flue gas collector seals, lip seal and insulation
- Worn or loose flue gas collector gasket
- Leaking lip seal at the boiler flue connection
- Water side fitting leak
- Damaged or loose thermal insulation
How to fix check flue gas collector seals, lip seal and insulation: step by step
- Check the gasket/seal between flue gas collector C and boiler body B for tightness.
- Check lip seal D on the boiler flue connection.
- Under full load, use an inspection mirror if needed. Remove thermal insulation parts if required.
- Before removing the flue gas collector, unplug flue gas temperature sensor F.
- If the collector seal leaks, retighten it at tensioning toggles E or replace it.
- Replace lip seal D if it leaks.
- Check water side fittings and replace seals or gaskets if needed.
- Check that the boiler insulation fits well. Correct the fit or replace damaged parts.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.