Viessmann Boiler: Check fixed high limit
Check fixed high limit on a Viessmann boiler: Check the fixed high limit if the burner control cannot be reset after a fault shutdown, although the boiler water temperature is below approx. 167°F (75°C).
Applies to: Fixed high limit on Vitodens 200-W B2HA
Common causes of check fixed high limit
- Fixed high limit open or defective after a fault shutdown
How to fix check fixed high limit: step by step
- Disconnect main power before opening the boiler.
- Remove the cables from the fixed high limit.
- Check continuity of the fixed high limit with a multimeter.
- Remove and replace a defective fixed high limit.
- After startup, press reset button R on the boiler control.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 81. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.