Viessmann Boiler: Check expansion tank, low water cut-off and pumps
Check expansion tank, low water cut-off and pumps on a Viessmann boiler: Confirm water system components are working and the system is charged.
Applies to: Vitorond 100 VR1
Common causes of check expansion tank, low water cut-off and pumps
- Low fill pressure usually means water loss through leakage.
How to fix check expansion tank, low water cut-off and pumps: step by step
- Follow the maintenance instructions supplied with the expansion tank, low water cut-off, pumps and zone valves.
- Flush float-type low water cut-offs if used.
- Check that the cold water fill pressure is 10 to 15 psi.
- Correct all leaks and follow the automatic fill valve instructions.
- Lubricate oil-lubricated pumps if used.
- On older non-diaphragm tanks, confirm the correct water level.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100, VR1 installation and service instructions, p. 47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.