Viessmann Boiler: Check expansion tank and system water pressure
Check expansion tank and system water pressure on a Viessmann boiler: Check the cold-system fill pressure, the diaphragm expansion tank pre-charge and the safety header. Do all checks on a cold system.
Applies to: Hydronic system pressure
Common causes of check expansion tank and system water pressure
- Low fill pressure usually means water is leaking from the system.
- Expansion tank inlet pressure below static pressure.
How to fix check expansion tank and system water pressure: step by step
- Use a cold system only and follow the expansion tank maker's instructions.
- Confirm the cold fill pressure is 12 to 15 psig. Correct any leaks.
- Confirm the safety header pressure gauge, air vent and relief valve operate, and that the relief valve does not leak.
- To re-charge the expansion tank, drain the system or close the tank cap valve and bleed the pressure to 0 on the gauge.
- If the tank inlet pressure is below static pressure, add nitrogen until it is 0.1 to 0.2 bar (1.5 to 3 psig) above static pressure.
- Top up with water until the cold fill pressure is 0.1 to 0.2 bar (1.5 to 3 psig) above the tank inlet pressure.
- Keep maximum operating pressure at or below 5 bar (75 psig).
- Flush float-type low water cut-offs if used.
- For an older non-diaphragm tank, check the water level is approximately half full.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2A service instructions, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.