Check diaphragm expansion tank and system pressure on a Viessmann boiler: Perform with the system cold.
Applies to: Vitodens 200-W B2HA 19, 28, 35
Common causes of check diaphragm expansion tank and system pressure
- Lower manometer reading usually means water loss from leakage
How to fix check diaphragm expansion tank and system pressure: step by step
- Drain the boiler or system and reduce pressure until the manometer reads 0.
- If tank nitrogen pressure is below system static pressure, charge the membrane to slightly above system pressure.
- Top up with water until the fill pressure is about 3 psig above static pressure.
- On first start-up, mark this value as the minimum fill pressure on the manometer.
- Repair all leaks.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.