Viessmann Boiler: Check DHW tank temperature sensor
Check DHW tank temperature sensor on a Viessmann boiler: Measure the DHW sensor resistance and compare it with the current DHW temperature.
Applies to: DHW tank temperature sensor
How to fix check dhw tank temperature sensor: step by step
- Disconnect the sensor plug in the terminal compartment.
- Measure the resistance at terminals 1 and 2 of the plug.
- Compare the reading with the current DHW temperature using the table.
- If the values differ significantly, check the installation.
- Replace the sensor if the installation is correct and the reading is still wrong.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Source: Vitotronic 200 service instructions, p. 70. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.