Viessmann Boiler: Check condensate drain and trap
Check condensate drain and trap on a Viessmann boiler: Keeps condensate draining freely to avoid a burner shutdown.
Applies to: Vitodens 200-W B2HA 19, 28, 35
Common causes of check condensate drain and trap
- Condensate not draining freely, which builds up in the bottom of the boiler and causes a fault message
How to fix check condensate drain and trap: step by step
- Remove retaining clip A from condensate trap B.
- Disconnect flexible discharge tubing C from the trap.
- Remove the condensate trap from the boiler.
- Clean out debris and refill the trap with water.
- Reinstall the trap and secure it with the clip.
- Reconnect the flexible discharge tubing.
- Do not connect other drains, such as a water softener backwash pipe, to the condensate drain.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.