Viessmann Boiler: Check condensate drain and clean condensate trap
Check condensate drain and clean condensate trap on a Viessmann boiler: Condensate must drain freely. If it does not, it builds up in the bottom of the boiler and causes a burner shut-down fault.
Applies to: Vitodens 200-W B2HA 45, 60
Common causes of check condensate drain and clean condensate trap
- Blocked or debris-filled condensate trap
- Restricted drain line
How to fix check condensate drain and clean condensate trap: step by step
- Remove retaining clip A from condensate trap B.
- Disconnect flexible discharge tubing C from the trap.
- Remove the trap from the boiler.
- Clean out any debris and refill the trap with water.
- Reinstall the trap and secure with clip A.
- Reconnect the flexible discharge tubing.
- Do not connect drain from other appliances such as water softener backwash.
- Keep the air gap and vent between the trap and neutralization unit (if fitted).
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.