Viessmann Boiler: Check coaxial venting for leaks
Check coaxial venting for leaks on a Viessmann boiler: Simplified leak test by measuring CO2 or O2 in the combustion air in the coaxial gap of the air intake pipe.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
How to fix check coaxial venting for leaks: step by step
- Measure CO2 in the combustion air in the coaxial gap of the air intake pipe.
- Vent pipe is acceptable if CO2 is no higher than 0.2% or O2 is no lower than 20.6%.
- If CO2 is higher or O2 is lower, check the venting system thoroughly.
- Use the two measurement ports on the vent pipe adaptor: one for combustion air intake and one for flue gas.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.