Viessmann Boiler: Check CO2 setting at low and high fire
Check CO2 setting at low and high fire on a Viessmann boiler: Verify combustion by measuring CO2 and O2 at low fire and high fire using the actuator test.
Applies to: Vitodens 200-W B2HA 80 to 100 and 285 to 352
Common causes of check co2 setting at low and high fire
- Venting leak
- Boiler set for wrong gas type
- Readings more than 1% outside range
How to fix check co2 setting at low and high fire: step by step
- Connect a flue gas analyzer to the test port at the boiler vent pipe adaptor.
- Open the gas shut-off valve, start the boiler and create a heat demand.
- Enter the service menu and open the actuator test.
- For low fire, select Base load OFF, then Base load ON appears and the burner runs at low fire.
- Measure CO2 and O2 and compare to the ranges.
- End with 'all actuators off' and record the values.
- For high fire, select Full load OFF, then Full load ON appears and the burner runs at high fire.
- Measure CO2 and O2 again and compare to the ranges.
- Exit the actuator test and record the values in the Maintenance Record on page 102.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.