Viessmann Boiler: Check burner refractory ring and cylinder burner
Check burner refractory ring and cylinder burner on a Viessmann boiler: Check the burner refractory ring and cylinder burner assembly for damage and replace if needed.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix check burner refractory ring and cylinder burner: step by step
- Remove the electrode block and ionization electrode.
- Undo the three retaining clips and remove the refractory ring.
- Loosen the four Torx screws and remove the cylinder burner assembly and assembly gasket.
- Fit the new cylinder burner assembly and new gasket. Tighten to 3.3 lb.ft (4.5 Nm) with a calibrated torque wrench.
- Refit the refractory ring and secure with the retaining clips.
- Refit the electrode block and ionization electrode. Tighten to 2.6 lb.ft (3.5 Nm) with a calibrated torque wrench.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.