Viessmann Boiler: Check burner refractory, cylinder burner and flue gas flapper
Check burner refractory, cylinder burner and flue gas flapper on a Viessmann boiler: Inspection and replacement of the burner refractory, cylinder burner assembly and flue gas flapper.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix check burner refractory, cylinder burner and flue gas flapper: step by step
- Check the burner refractory ring C and cylinder burner E for damage. Replace if needed.
- Remove electrode block and ionization electrode A.
- Undo the three clips B and remove refractory ring C.
- Loosen the four Torx screws D and remove cylinder burner E and assembly gasket F.
- Fit new cylinder burner and new gasket. Tighten to 3.3 lb.ft (4.5 Nm) with a calibrated torque wrench.
- Reinstall refractory ring C and secure with clips B.
- Reinstall electrode block and ionization electrode A. Tighten to 2.6 lb.ft (3.5 Nm).
- To check the flue gas flapper, remove fan A (three screws), remove flapper B and check flapper and gasket for dirt and damage. Replace if needed.
- Refit flapper B and refit fan A with three screws to 2.2 lb.ft (3.0 Nm).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.