Viessmann Boiler: Check burner door gasket and burner gauze assembly
Check burner door gasket and burner gauze assembly on a Viessmann boiler: Replace the burner gauze and gasket if damaged.
Applies to: Vitodens 222-F B2TB 19, 35, 68, 125
How to fix check burner door gasket and burner gauze assembly: step by step
- Check burner door gasket A and cylinder burner assembly E for damage. Replace if needed.
- Remove the electrode block and ionization electrode B.
- Undo three retaining clips C and remove the thermal refractory ring D.
- Undo four Torx screws and remove burner gauze assembly E with gasket F.
- Fit a new gauze assembly and new gasket. Tighten to 31 lb.in (3.5 Nm).
- Refit refractory ring A and secure with clip C.
- Refit the electrode block and ionization electrode B and tighten to 40 lb.in (4.5 Nm).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
Source: Vitodens 222-F B2TB service instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.