Viessmann Boiler: Check boiler water temperature sensor, DHW tank sensor or supply/low-loss header sensor
Check boiler water temperature sensor, DHW tank sensor or supply/low-loss header sensor on a Viessmann boiler: Check sensor resistance and compare with the curve. Sensor type is NTC 10 kΩ. Only one supply temperature sensor or low-loss header sensor may be used.
Applies to: Boiler temperature sensor, DHW tank sensor, supply or low-loss header sensor
Common causes of check boiler water temperature sensor, dhw tank sensor or supply/low-loss header sensor
- Faulty boiler water temperature sensor
- Faulty DHW tank temperature sensor
- Faulty supply or low-loss header temperature sensor
How to fix check boiler water temperature sensor, dhw tank sensor or supply/low-loss header sensor: step by step
- Drain the boiler before replacing a sensor, as the sensors are immersed in heating water (scald risk).
- Boiler temperature sensor: remove lead to sensor and measure resistance.
- DHW tank sensor: pull plug from cable harness at control unit and measure resistance.
- Supply or low-loss header sensor: pull plug X3 and measure across terminals X3.4 and X3.5.
- Compare values with the curve and replace the sensor if deviation is severe.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 86. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.