Updated · by Aurora Star Tech Inc.

Check and set expansion tank precharge on a Viessmann boiler: The expansion tank is precharged to 12 psi at the factory. Its Schrader valve is reached from the bottom of the boiler.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotron 100 VLN2 expansion tank

How to fix check and set expansion tank precharge: step by step

  1. Access the Schrader valve from the bottom of the boiler.
  2. Connect a pressure gauge to read the tank pressure.
  3. Use a pump to add air if the precharge is low.
  4. Match the precharge to the system pressure requirement if needed.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

VLN2 04VLN2 06VLN2 08VLN2 12VLN2 14.4

More commissioning tips for boiler

Source: Vitotron 100 VLN2 installation and service instructions, p. 8-9. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.