Viessmann Boiler: Check and service the neutralisation unit (if fitted)
Check and service the neutralisation unit (if fitted) on a Viessmann boiler: Applies when a neutralisation unit accessory is installed. The granulate is used up as it neutralises the condensate.
Applies to: Vitodens 100-W, WB1B with neutralisation unit
Common causes of check and service the neutralisation unit (if fitted)
- Condensate pH below 6.5
- Contaminated neutralisation unit
How to fix check and service the neutralisation unit (if fitted): step by step
- Check the condensate pH with a pH test strip (field supplied). If pH is below 6.5, replace the granulate.
- If contaminated, rinse the unit with tap water.
- Add granulate up to the mark on the cartridge. Do not fill below the red minimum filling level marking.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 70. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.