Viessmann Boiler: Check and reverse mixing valve motor rotation

Updated · by Aurora Star Tech Inc.

Check and reverse mixing valve motor rotation on a Viessmann boiler: The boiler runs a self-test at power-up in which the mixing valve opens and closes again. Use this with a manual test to confirm the motor direction. The motor direction is reversed by switching two core wires at a plug.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Extension kit with mixing valve

How to fix check and reverse mixing valve motor rotation: step by step

  1. Disconnect main power before opening the boiler.
  2. Watch the mixing valve during the self-test after switching on.
  3. Set the mixing valve manually to Open and check that the flow temperature sensor reads higher.
  4. To reverse the motor, remove the upper casing cover of the extension kit.
  5. At plug gS, switch the cores at terminals "|" and "~".
  6. Refit the casing cover and recheck operation.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More service & test modes tips for boiler

Source: Vitodens 200-W B2HA 45, 60 service instructions, p. 80. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.