Viessmann Boiler: Check and clean the burner tube
Check and clean the burner tube on a Viessmann boiler: Cleaning or replacing the burner gauze and gaskets. Keep insulation fibres out of the combustion chamber.
Applies to: CA3B 2.5 to 6.0
How to fix check and clean the burner tube: step by step
- Dismantle the burner first (see burner dismantling guide).
- Undo the 6 screws on the insulation ring. Tighten to 13 lb.in (1.5 Nm) on reassembly.
- Remove the insulation ring.
- Unscrew the burner gauze assembly. Vacuum it or replace it. Tighten to 7.5 lb.ft (10 Nm) on reassembly.
- Replace all gaskets.
- Reassemble the burner tube and burner in reverse order. Tighten to 7.5 lb.ft (10 Nm).
- Make sure no insulation fibres stick to the burner tube and none fall into the combustion chamber.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.