Viessmann Boiler: Check and clean condensate trap and drain
Check and clean condensate trap and drain on a Viessmann boiler: A blocked condensate drain makes condensate build up in the bottom of the boiler and causes a burner shut-down with a fault message.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
Common causes of check and clean condensate trap and drain
- Condensate does not drain freely
- Debris in the condensate trap
- Drain pipe connected to another appliance such as a water softener backwash line
How to fix check and clean condensate trap and drain: step by step
- Remove the retaining clip from the condensate trap and set it aside.
- Disconnect the flexible discharge tubing from the condensate trap.
- Remove the condensate trap from the boiler.
- Clean out debris and refill the trap with water.
- Reinstall the trap and secure it with the retaining clip.
- Reconnect the flexible discharge tubing to the trap.
- Confirm the drain has an air gap and is vented between the trap and any neutralization unit.
- Do not connect other drains, such as a water softener backwash pipe, to the condensate drain.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.