Viessmann Boiler: Check and adjust ignition and ionization electrodes
Check and adjust ignition and ionization electrodes on a Viessmann boiler: Electrode type depends on size: C is up to 35 kW (125 MBH), D is from 45 kW (160 MBH).
Applies to: Vitocrossal 300 CU3A ignition and ionization electrodes
Common causes of check and adjust ignition and ionization electrodes
- Worn or contaminated electrodes
- Electrode gap out of specification
How to fix check and adjust ignition and ionization electrodes: step by step
- Check electrodes for wear and contamination.
- Clean electrodes with a small brush (not wire) or sandpaper.
- Check electrode gaps against specification. Replace and align electrodes with new gaskets if gaps are wrong or electrodes are damaged.
- Tighten electrode fixing screws to 2.2 lb.ft (3.0 Nm).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.