Viessmann Boiler: Change the adjustable high limit
Change the adjustable high limit on a Viessmann boiler: Factory setting is 95 °C / 203 °F. Limit range is set by breaking off stop cams on the selector dial. Range A gives 75 to 195 °C (167 to 203 °F), range A and B gives 75 to 100 °C (167 to 212 °F), and range A, B and C gives 75 to 110 °C (167 to 230 °F). Note the setting of coding address 06 after changing.
Applies to: Vitotronic 100 GC1 adjustable high limit
How to fix change the adjustable high limit: step by step
- Disconnect power to the control and burner.
- Lever out and remove the selector knob 'R' behind the hinged cover with a suitable screwdriver.
- Break off the cams for the unwanted ranges from the stop dial with pointed pliers.
- Refit selector knob 'R' so the marking sits in the centre of the selected range.
- Record the setting of coding address 06.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.