Cascade strategy: net calorific 2 on a Viessmann boiler: An extra boiler starts only when all active burners at maximum output cannot reach the set supply temperature. A boiler shuts down when its burner is at minimum output because of a large negative deviation and output is still too high. Gives long burner run times. Net calorific 2 is the only strategy suitable for series arrangements.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocontrol-S VD2/CT3/CM2 cascade, series arrangement

How to fix cascade strategy: net calorific 2: step by step

  1. Start-up: the start-up integral must exceed the limit set in coding 45. The next boiler in the sequence then starts.
  2. Shutdown: the shutdown integral must exceed the limit set via coding 3d: 1, then the last boiler started is shut down.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1

Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 125, 127. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.