Viessmann Boiler: Cascade strategy: gross calorific (coding 3C: 0)
Cascade strategy: gross calorific (coding 3C: 0) on a Viessmann boiler: Operates as many boilers as possible at the lowest output for the best condensing effect. Gives long burner run times. Boilers are started by output statement and shut down by shutdown integral.
Applies to: Vitocontrol-S VD2/CT3/CM2 cascade, sequential control
How to fix cascade strategy: gross calorific (coding 3c: 0): step by step
- Start-up: a boiler starts (coding 3d: 1) when the current output can also be reached by the active boiler plus the next boiler in the sequence.
- Shutdown: the shutdown integral must exceed the limit set in coding 46, then the last boiler started is shut down.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 126. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.