Viessmann Boiler: Cascade control: set supply temperature and control types
Cascade control: set supply temperature and control types on a Viessmann boiler: The cascade regulates the supply temperature by starting or stopping burners or burner stages. The set supply temperature comes from the heating circuits, DHW demand and external demands such as coding 9b or the 0 to 10 V Input Module. Control types: stand-alone (parallel or series boiler arrangement, coding 3b 0 to 3) and sequential (coding 3b: 4), where the lead boiler can modulate and the others run in two stages.
Applies to: Vitocontrol-S VD2/CT3/CM2 cascade
How to fix cascade control: set supply temperature and control types: step by step
- Parallel stand-alone: coding 3b 0 without supply sensor, or 1 with supply sensor.
- Series stand-alone: coding 3b 2 without supply sensor, or 3 with supply sensor.
- Sequential: coding 3b 4.
- With a supply sensor, start-up and shutdown use the supply temperature deviation. Without it, they use the boiler water temperature and estimated average boiler temperature, counting only boilers whose isolation valve is open.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 124-125. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.