Calculate the heating curve slope on a Viessmann boiler: Slope = (design supply temperature - WWSD temperature) divided by (WWSD temperature - design outdoor temperature). Worked example from the manual: design outdoor 5 F (-15 C), WWSD 70 F (21 C), design supply 160 F (71 C). Slope = (160 - 70) / (70 - 5) = 90 / 65 = 1.4, which is then set on S4 (nearest value on the dial is 1.4 or the next available setting from the table).

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 100 KW10B heating curve

How to fix calculate the heating curve slope: step by step

  1. Find the design supply temperature and the design outdoor temperature for the building.
  2. Set the WWSD temperature on S5 (factory 70 F / 21 C).
  3. Apply the formula to get the slope.
  4. Set S4 to the matching slope value.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

GC1KW10B

Source: Vitotronic 100 KW10B installation manual, p. 19. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.