Viessmann Boiler: Burner reassembly and CO2 check after cleaning
Burner reassembly and CO2 check after cleaning on a Viessmann boiler: Tighten fasteners to specified torque and check gas tightness before starting. Leak detection spray can cause faulty operation.
Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
How to fix burner reassembly and co2 check after cleaning: step by step
- Position the burner plate with burner mesh on the 8 studs and tighten nuts to 7.3 lb.ft (10 Nm).
- Place the upper burner section on the burner plate and tighten M10 nuts to 7.3 lb.ft (10 Nm).
- Push on the ignition and ionization electrode connectors.
- Insert connectors at the plug-in panel and burner control unit; connect the mains plug last.
- Fit the gas connection pipe and check the fitting for gas tightness.
- Keep leak detection spray away from electrical contacts.
- Start the burner and run a function test.
- Measure CO2 after each burner dismantling per pages 66 and 67, and record it in the maintenance record on page 158.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 74. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.