Viessmann Boiler: Burner motor power supply, 3PH 208/460/575 V (VD2/VD2A/CT3)
Burner motor power supply, 3PH 208/460/575 V (VD2/VD2A/CT3) on a Viessmann boiler: Wiring of the burner motor for three-phase burners at 208, 460 or 575 V, including the rotation check.
Applies to: Three-phase burner motor, 208, 460 or 575 V (VD2/VD2A/CT3)
How to fix burner motor power supply, 3ph 208/460/575 v (vd2/vd2a/ct3): step by step
- Disconnect power to the burner and the boiler control.
- Connect 3PH power to terminals 21, 22, 23 and 24 on the DIN rail inside the connection enclosure.
- Provide a fuseable disconnect according to local codes. Size fuses and wire gauge per the burner manual.
- Connect the supplied power cable to the motor terminals on the burner.
- Connect the cable plug to the socket on the DIN rail in the connection enclosure.
- During commissioning, check motor rotation against the arrow on the burner.
- If the motor turns the wrong way, disconnect power and swap wires BK1 and BK2 on the burner terminals.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 65. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.