Viessmann Boiler: Burner motor power supply, 3-phase 208, 460 or 575 V
Burner motor power supply, 3-phase 208, 460 or 575 V on a Viessmann boiler: Power the burner motor from a 3-phase supply. The motor rotation must be checked during commissioning.
Applies to: Burners with 3PH 208, 460 or 575 V supply
How to fix burner motor power supply, 3-phase 208, 460 or 575 v: step by step
- Disconnect power to the burner and the boiler control.
- Connect 3-phase power to terminals 21, 22, 23 and 24 on the DIN rail in the connection enclosure. Fit a fuseable disconnect according to local codes.
- Connect the supplied power cable to the motor terminals on the burner.
- Plug the cable plug into the socket on the DIN rail in the connection enclosure.
- During commissioning, check the motor rotation against the direction shown on the burner.
- If the motor turns the wrong way, disconnect power and reverse wires BK1 and BK2 on the burner terminals.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.