Viessmann Boiler: Burner motor power supply, 240 VAC 1PH (VD2/VD2A/CT3)
Burner motor power supply, 240 VAC 1PH (VD2/VD2A/CT3) on a Viessmann boiler: Wiring of the burner motor when the burner runs on 240 VAC single-phase power through a conduit connection.
Applies to: Burner motor, 240 VAC 1PH, conduit connection (VD2/VD2A/CT3)
How to fix burner motor power supply, 240 vac 1ph (vd2/vd2a/ct3): step by step
- Disconnect power to the burner and the boiler control.
- Connect 240 VAC power to terminals 21, 22 and 23 on the DIN rail inside the connection enclosure.
- Provide a fuseable disconnect according to local codes. Size fuses and wire gauge per the burner manual.
- Connect the supplied power cable to the motor terminals on the burner.
- Connect the cable plug to the socket on the DIN rail in the connection enclosure.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.