Viessmann Boiler: Burner harness and cable strap routing
Burner harness and cable strap routing on a Viessmann boiler: Secure the burner harness to the side panel with the supplied cable straps. Leave no slack so the burner door can swing open without unplugging the harness.
Applies to: Burner wiring harness on VR1 boilers
How to fix burner harness and cable strap routing: step by step
- Secure the control harness with the two supplied cable straps.
- Coil the extra harness on the side panel with no slack.
- For Beckett or Carlin burners, cut the harness length to 6 in. for the burner junction box under the primary control.
- For Riello burners, leave the harness at full length (marked as Riello only).
- Do not run conduit through the cover mounting plate. Pass it through the front opening or a side knockout into the 4x4 burner junction box.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 VR1 installation and service manual, p. 29 and p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.