Viessmann Boiler: Burner harness and cable strap routing

Updated · by Aurora Star Tech Inc.

Burner harness and cable strap routing on a Viessmann boiler: Secure the burner harness to the side panel with the supplied cable straps. Leave no slack so the burner door can swing open without unplugging the harness.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Burner wiring harness on VR1 boilers

How to fix burner harness and cable strap routing: step by step

  1. Secure the control harness with the two supplied cable straps.
  2. Coil the extra harness on the side panel with no slack.
  3. For Beckett or Carlin burners, cut the harness length to 6 in. for the burner junction box under the primary control.
  4. For Riello burners, leave the harness at full length (marked as Riello only).
  5. Do not run conduit through the cover mounting plate. Pass it through the front opening or a side knockout into the 4x4 burner junction box.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitorond 100 VR1 installation and service manual, p. 29 and p. 30. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.