Viessmann Boiler: Burner does not start or starts intermittently (red fault LED flashing)
Burner does not start or starts intermittently (red fault LED flashing) on a Viessmann boiler: Burner fault LED flashes and the burner starts and stops.
Applies to: Vitotronic 100 KW10B with burner
Common causes of burner does not start or starts intermittently (red fault led flashing)
- Burner is not electrically connected.
- Fixed high limit (FHL) has tripped.
How to fix burner does not start or starts intermittently (red fault led flashing): step by step
- Confirm the 7-pole plug-in connection to the burner and power venter is made.
- Reset the FHL by pressing in the pin labelled E with a ballpoint pen.
- If a click is heard, the limit had tripped; find and correct the cause before restarting.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 KW10B installation, start-up and service instructions, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.