Viessmann Boiler: Burner connection and burner control wiring (CM2, plug-in burner)
Burner connection and burner control wiring (CM2, plug-in burner) on a Viessmann boiler: For burners with plug-in connection. Burner cables come with the Vitotronic. Connect the burner per local codes. Terminal 1 is the phase from the fixed high limit, terminal 2 is modulating down, and terminal 3 is modulating up or 2nd stage ON. Terminal S3 takes the burner fault signal and B4 takes the burner hours counter. T1 and T2 are the control circuit. Colour codes: BK black, BN brown, BU blue.
Applies to: Vitotronic 300 GW2 with CM2 control, plug-in burner connection
How to fix burner connection and burner control wiring (cm2, plug-in burner): step by step
- Disconnect power to the burner and the boiler control.
- Connect the 7-pole burner plug to the matching counter plug on the boiler control unit.
- Connect the 3-pole burner plug to the matching counter plug on the boiler control unit.
- Connect the 7-pole plug and the 3-pole plug to the burner.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.