Viessmann Boiler: Boiler water temperature too high or too low
Boiler water temperature too high or too low on a Viessmann boiler: Check whether the setpoint is wrong or whether the temperature measurement is at fault.
Applies to: Vitotronic 200 KW2 boiler water temperature control
Common causes of boiler water temperature too high or too low
- Wrong timer, heating curve or coding address settings
- Faulty setpoint selector or remote control
- Fault in the remote control connecting cable
- Faulty boiler temperature sensor
- Electro-mechanical adjustable high limit set incorrectly
How to fix boiler water temperature too high or too low: step by step
- Compare the current boiler water temperature with the desired value.
- If the desired value is wrong: check timer, heating curves and coding addresses.
- Check the setpoint selector and remote control (if fitted). Set a very high day temperature and a very low night temperature, and set the time so the operation changes from normal room temperature to reduced room temperature in a few minutes.
- Confirm the switchover causes a clear change in boiler water setpoint. If not, connect the remote control with its fixture directly to the Vitotronic and repeat the test.
- If the setpoint is now correct, the fault is in the remote control connecting cable.
- If the setpoint is still wrong, recheck the equipment settings and remote control and replace the remote control if needed.
- If the desired value is correct: measure the boiler water temperature with a thermometer in the sensor well and compare it with the sensor resistance curve.
- Check the cut-off point of the electro-mechanical adjustable high limit.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Source: Viessmann Vitotronic 200 service instructions, p. 42. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.