Viessmann Boiler: Boiler sequence and ECO thresholds
Boiler sequence and ECO thresholds on a Viessmann boiler: The control picks boiler sequence from the cascade codes and internal calculations. ECO thresholds can block or enable each boiler based on outside temperature. ECO control is disabled if the boiler is needed to reach set supply temperature after enabled boilers have failed. The lead boiler always stays active.
Applies to: Vitotronic 300-K cascade
How to fix boiler sequence and eco thresholds: step by step
- Review codes 38 (lead boiler change and sequence), 39 and 3A (permanent lead and last boiler).
- Set ECO thresholds at codes 41 to 44, 65, 6F, 74 and 7D as needed.
- To set the sequence in the extended menu, open the menu, select Boiler sequence, set the required sequence, then press OK.
- Note that the boiler sequence settings require the Viessmann LON system where marked.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
MW1SVitotronic 300-K, type MW2B
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.